10 watts/ft 120 volt mid temperature, self regulating heat trace cable with fluropolymer jacket.
Ideal for pipe tracing, freeze protection, and low temperature process maintenance applications up to 250°F (120°C).
Self-limiting: Automatically adjusts heat output based on surface temperature.
Safe to overlap and insulate.
Can be cut-to-length and terminated in the field.
No temperature controller is required. (If a specific process temperature is needed, a temperature controller is required.)
Specifications:
- Continuous maintenance temperature: 250°F (120°C) maximum
- Intermittent exposure temperature: 366°F (185°C) maximum; -40°F (-40°C) minumum
- 5, 10, or 15 watts/ft (16, 33, 49 watts/m)
- Supply voltages: 110 – 120VAC or 208 – 277VAC
- Moisture, chemical, and flame resistant
- 16AWG bus wires
- Tinned copper braid resistance: 0.003 ohms/ft (0.010 ohms/m)
- T-Rating: T3**
** Electrical equipment T-rating codes define the maximum surface temperature that equipment will reach. It is used in hazardous (classified) area applications.

Outer Layer Options
| Description | Dimensions | Purpose |
| Tinned Copper Metal Braid | 0.2″ x 0.6″ (6mm x 15mm) |
Ordinary applications |
| Tinned Copper Metal Braid with Fluoropolymer Overjacket | 0.2″ x 0.6″ (6mm x 15mm) |
For use in strong chemical environments (i.e. strong acids) |
Maximum Circuit Length in Feet per Circuit Breaker Size
| Heat Cable Type | Circuit Breaker Size | Start-up Temperature | ||
| 50°F (10°C) |
0°F (-20°C) |
-40°F (-40°C) |
||
| 5 watt 120 volt | 15 amp 20 amp 30 amp |
150 200 240 |
135 180 220 |
130 170 210 |
| 5 watt 240 volt | 15 amp 20 amp 30 amp |
250 330 480 |
230 305 440 |
220 295 420 |
| 10 watt 120 volt | 15 amp 20 amp 30 amp |
90 120 180 |
85 110 165 |
80 105 160 |
| 10 watt 240 volt | 15 amp 20 amp 30 amp |
140 190 280 |
130 175 260 |
125 170 250 |
| 15 watt 120 volt | 15 amp 20 amp 30 amp |
70 90 130 |
65 85 125 |
60 80 120 |
| 15 watt 240 volt | 15 amp 20 amp 30 amp |
100 135 200 |
95 125 185 |
90 120 180 |
Note: Special consideration must be given for the circuit breaker due to the high initial in-rush currents.
Voltage Adjustment
| Power Adjustment Factor | ||
| Product Type | 208 VAC | 277 VAC |
| 5 watt 240 volt | 0.78 | 1.25 |
| 10 watt 240 volt | 0.86 | 1.16 |
| 15 watt 240 volt | 0.92 | 1.09 |