Cooling Tower Control Panel Specifications
-
Solid-State Control: Pre-set 45° F ON/OFF temperature control with 5° F switching differential and built-in low water cutoff. Circuit board LED’s provide visual indication of heater-on and liquid level status.
-
Ambient Temperature Range: -40° F to 150° F
-
Fail Safe: Output relay is de-energized if the input sensor is either open or short-circuited. This prevents heater burnout problems.
-
NEMA 4X enclosure with pre-mounted electrical hubs for conduit connections.
-
Single probe to sense both water temperature and water level. Sensor probe supplied with 12-foot outdoor rated cord pre-connected to control panel. Probe also supplied with PVC hub connector for attachments through cooling tower basin wall.
-
Nameplate showing maximum KW and amp ratings at system volts/phase.
-
System Wiring Diagram.
-
Installation and Operating Instructions.
-
Rated for maximum of 40 amps or 50 amps with disconnect switch when specified.
-
Suitable for multiple heaters per basin (maximum of 2 on 40 amp panel).
-
Disconnect switch with door interlock and operator handle, which can be padlocked in the “OFF” position.
- Dimensions: 8″ x 10″ x 6″ for 40 amp size, 10″ x 12″ x 7″ for 50 amp size, 14″ x 16″ x 8″ for two circuits
-
Control panels rated greater than 50 amps are supplied with two circuits and offered either with built-in fusing or a circuit breaker for each circuit.