Tinned copper braid with FEP overjacket for harsh environments.
Circuit load: 0.033 amps per foot
Maximum circuit length: 350 foot
Maintains temp to 320°F
Jacket withstands temp to 392°F

Our CWJ12 general purpose, constant wattage heating cable is a proven, reliable solution for industrial process temperature maintenance and freeze protection. CWJ12 features a parallel heating core that produces uniform thermal output over its entire length. Using a single power point, you can easily configure and install a heat tracing system as short as several feet or as long as 780 feet right in the field.
- Uniform Thermal Output, Low Energy Cost
- No Inrush at Any Ambient
- Maximum Exposure Temperature, Power Off, 392°F (200°C)
- Steam Cleanable on Process Equipment Up to 190 PSIG (Power Off)
- Approximate Size 1/4″W x 1/8″H
- Minimum Bend Radius 1-1/4″
- For Use on Metallic Pipes
WARNING — A ground fault protection device is required by NEC to minimize the danger of fire if the heating cable is damaged or improperly installed. A minimum trip level of 30mA is recommended to minimize nuisance tripping.
| Model | Output | Voltage | Circuit Load | Max.Circuit Length |
| CWJ124120 | 4 W/Ft. | 120 volt | 0.033 Amps/Ft. | 350 Ft. |
| CWJ128120 | 8 W/Ft. | 120 volt | 0.067 Amps/Ft. | 240 Ft. |
| CWJ1212120 | 12 W/Ft. | 120 volt | 0.100 Amps/Ft. | 200 Ft. |
| CWJ124240 | 4 W/Ft. | 240 volt | 0.017 Amps/Ft. | 700 Ft. |
| CWJ128240 | 8 W/Ft. | 240 volt | 0.033 Amps/Ft. | 480 Ft. |
| CWJ1212240 | 12 W/Ft. | 240 volt | 0.050 Amps/Ft. | 400 Ft. |
| CWJ1212480 | 12 W/Ft. | 480 volt | 0.025 Amps/Ft. | 780 Ft. |